Federal agencies Injury prevention

NFPA 70E: Five key revisions for 2021

NFPA
Photo: chinaface/iStockphoto

From the beginning

Article 110, titled “General Requirements for Electrical Safety-Related Work Practices,” is where it all begins for workers.

“Article 110 applies to everything,” Coache said. “It’s the basis for what you should be doing.” Changes to the article involved reorganizing it to ensure the requirements are in a proper progression. This included moving the general principles of lockout/tagout from Section 120.2 and energized work requirements from Section 130.2.

“They’re moving things over to make the standard more logical,” Coache said.

The article contains a new subsection – 110.5(K) – that requires an employer’s electrical safety program to “include an electrically safe work condition policy.”

Capacitors get attention

Article 360, titled “Safety-Related Requirements for Capacitors,” puts added attention on these energy storage devices that are used in many different systems, such as conveyers, heating, cooling and airflow.

“Capacitors were always included, but now they’ve got their own article,” Coache said. “With all the alternate energies, there are a lot of capacitor systems being used. If you shut them off, they still have power. It’s like a battery, essentially.

“The public, the industry and the technical committee felt that a full, dedicated article to capacitors was important. There are stored-energy capacitors used in lots of systems.”

The article includes measures to keep workers safe, perform a risk assessment and establish an electrically safe work condition for a capacitor.

Energy threshold change

Section 350.9 revises energy thresholds for electrical equipment and systems in laboratories (50 volts and 5 milliamperes for alternating current; 100 volts and 40 milliamperes for direct current) unless appropriate controls are implemented.

With the addition of Article 360, the capacitive circuit threshold was deleted to avoid duplication and potential confusion, according to NFPA.

Arc flash incident likelihoods

When it comes to arc flash hazards, “you’re better off assuming there is one until you know there isn’t one,” Coache said.

To that end, the 2021 edition of NFPA 70E includes a revised Table 130.5(C), designed to be used to help estimate the likelihood of an arc flash incident. The reason for the change is to make sure the standard is being used properly.

“That table came about because of a change in learning how people were misusing the standard,” Coache said. “It’s to pass the concept on that you need to make sure that the likelihood of an occurrence doesn’t exist for your piece of equipment. The people who write the standard and the public who share input don’t have the ability to determine if your piece of equipment has an arc flash or not.”

Coache said NFPA 70E was never meant to make individual determinations on equipment. For example, the standard isn’t able to take into consideration if a circuit breaker or other electrical equipment is poorly maintained.

“People were blindly going into the standard and using the tables without considering the likelihood of an occurrence,” he said. “The standard is trying to guide people more into making better calls than they had historically.”

The table comprises more than 30 tasks to determine arc flash likelihood, including a new entry on the initial operation of a circuit breaker or switch after installation and again after maintenance on the equipment, because each present a higher likelihood of an incident.

Hazardous work

In Article 130, “Work Involving Electrical Hazards,” two sections – 130.1: General and 130.2: Energized Electrical Work Permit – have been rewritten to accommodate information moved from other portions of NFPA 70E.

The result is more details focused on safety-related work practices, assessments, precautions and procedures when an electrically safe work condition can’t be established, along with elements and exceptions of a work permit.

Post a comment to this article

Safety+Health welcomes comments that promote respectful dialogue. Please stay on topic. Comments that contain personal attacks, profanity or abusive language – or those aggressively promoting products or services – will be removed. We reserve the right to determine which comments violate our comment policy. (Anonymous comments are welcome; merely skip the “name” field in the comment box. An email address is required but will not be included with your comment.)